Programming a setpoint pulse for controlling MW output of generator
$250-750 USD
Płatność przy odbiorze
The NovaTech RTU communicates with the SEL RTU through DNP3 and does not directly RAISE or LOWER the setpoint. The NovaTech provides the setpoint for the SEL to RAISE and LOWER the actual controller setpoint using the MODBUS coils.
The program that is needed requires taking a DNP3 SetPoint value from the NovaTech RTU (this tag does not exist today and must be created on both ends) and initiate a RAISE or LOWER of the MW setpoint by clearing (operClear) and then setting (operSet) the associated MODBUS Coil (CT1LOADRAISE or CT1LOADLOWER). For each of the MODBUS devices, the SEL is the client and the Controllers are the servers. For DNP3, the SEL is the server and the NovaTech is the client.
RTAC project file will be provided after project has been awarded to successful bidder.
*** REQUIREMENT ***
Must have SEL-5033 AcSELerator-RTAC softwware or ability to download from SEL.
Numer ID Projektu: #25848567